====== IQ3xcite ====== {{:suppliers:trend_control_systems_ltd:iq3xcite_large.png?200|}} The Trend IQ3xcite building energy management system controller uses BACnet IP, TCP/IP, Ethernet networking technologies as well as Trend’s proprietary communications. Its secure, embedded Web server delivers user-specific Web pages to a PC or mobile device running familiar, easy-to-use Internet browser software. The IQ3xcite’s graphics are easy to understand and navigate. This controller is virtually plug-and-play; its modular design accommodates any expansion or configuration a user needs. The DIN-rail-mounted IQ3xcite’s basic version offers ten inputs and six outputs; an expandable version can have up to 128 points by adding I/O modules. A user can network more than 16,000 IQ3xcite controllers. ===== Features ===== * BACnet-enabled and adjustable BACnet priorities * Ethernet (10Mbps) network with TCP/IP protocol * Embedded Web server * Secure monitoring and control from a Web browser * 10 universal inputs and 6 analog outputs * Expandable to 128 points using optional I/O modules * EIA-232 local supervisor port * Local display (SDU-xcite) * Small footprint with DIN-rail mounting * Multiple language support * Support for XML Web services {{:suppliers:trend_control_systems_ltd:ds_iq3xcite.pdf|}}