PXC3.E75A

Room automation station BACnet / IP and DALI, for up to 8 rooms / 16 room segments

Known BACnet Compatibility Issue

As of October 2016:

Device doesn't respect the requested segmented window size. It asks for 4, but wait for an ACK after 2 :

Consequences : communication will timeout, or take much longer if the client device has an automatic fallback.